Akasol Akasystem 15 OEM 50 PRC

Compatible batteries~

AKASOL AKASYSTEM 15 OEM 50 PRC — a single-tray, 655 V nominal NMC pack (180 cells, 50 Ah, ~33 kWh) with one BMM01 controller.

Note: Only the single-tray BMM01 variant is implemented. Multi-tray systems use a different addressing scheme and are not covered.

Physical Dimensions~

Parameter Value
Pack Size (L × W × H) 1700 × 700 × 150 mm
Weight 270 kg

Electrical data~

Parameter Value
Nominal voltage 655 V
Voltage range 540 – 756 V
Capacity 50 Ah
Energy 33 kWh
Cells 180 in series (15 modules × 12s1p)
Chemistry NMC
Internal HV fuse 200 A
Continuous charge power 45 kW
Continuous discharge power 50 kW (RMS)
Protection class IP67 / IP6K9K
Operating temperature range −30 °C to +60 °C

The pack reports far higher current limits than a typical inverter battery port accepts (roughly 137 A charge / 180 A discharge have been seen on the bus). The driver clamps to 30 A before the value reaches the datalayer.

Special considerations~

  • The CAN bus is 250kbps on this battery, so it needs to be on its own separate CAN network
  • Startup sequence: The battery requires a specific startup signal via KL30 / KL30_Safe / KL15. This has been implemented via the Pre/Neg/Pos contactor pins used in BE
  • The LV supply is nominally 24 V, not 12 V. The manual's integration chapter specifies 24 V, while the safety chapter refers to the safe-power signal as "12 V or 24 V". No voltage window is published, and the KL30 min/max thresholds are listed as optional parameters, so they may vary per unit. 24 V is the documented choice and is what this installation runs
  • The pack closes its own HV contactors over CAN once it reaches Operational. GPIO contactor control in BE must stay disabled — the driver uses those three pins for KL30 / KL30_Safe / Wake instead
  • The HV interlock (HVIL) loop must be closed, or the contactors will not close
  • Liquid cooled. The battery must be kept inside its temperature range by an external thermal circuit

Software configuration~

For this battery type, use the option called "AKASOL" under the "Battery Protocol" section.

The three discrete control signals are taken from the HAL's contactor pins, so the mapping follows whatever the selected board defines:

BE HAL pin Akasol signal
PRECHARGE_PIN() KL30
NEGATIVE_CONTACTOR_PIN() KL30_Safe
POSITIVE_CONTACTOR_PIN() KL15 / Battery Wake

On a LilyGo T-2CAN that is GPIO 21, 17 and 48 respectively.

The driver holds each step long enough for the previous one to settle: KL30_Safe alone for 500 ms, then KL30 added for 1000 ms, then Wake. Once the battery reports Standby it sends req_batuse=1. A VCU1_to_BMM01 frame goes out every 100 ms with a rolling alive counter.

An equipment stop withdraws req_batuse rather than dropping Battery_Wake, which is the shutdown order the manual specifies (chapter 6.2.2). The request is held until the pack current the battery itself reports has settled, so the contactors do not open under load.

Part numbers~

Part numbers below are the ones AKASOL specifies in the user manual (doc 3-024001TEN_0001 v1.2). Search links are generic — check the listing matches the exact part number before ordering.

Component Part Number Purchase Link
LV connector, Ampseal 23 (female, mates with BMU) — Tyco Electronics 770680-1 eBay / AliExpress
HV connector HVP800, 180° — Tyco Electronics 1-2177053-1 eBay / AliExpress
HV connector HVP800, 90° — Tyco Electronics 1-2141154-1 eBay / AliExpress
EloSeal contacts, 0.5 / 0.75 mm² — Tyco 5-1393462-5 eBay
EloPower contacts, 1.5 / 2.5 mm² — Tyco 5-1393462-9 eBay
Superseal / Ampseal crimp tool 16/18-20 — Tyco 354940-1 eBay

Wiring, Low voltage connector~

The BMU uses a 23-position Ampseal connector. Only the pins below are used for a single-tray installation — the manual is explicit that no other pin should be connected.

PIN SIGNAL PIN SIGNAL
1 PublicCAN_Low_In 13 KL30
2 PublicCAN_High_In 14 KL15_Wake
3 BMU-ID_3 15 KL15_Wake
4 KL30_Safe 16 PublicCAN_GND_In
5 KL30_Safe 17 PublicCAN_GND_In
6 PublicCAN_Low_Out 18 BMU-ID_2
7 PublicCAN_High_Out 19 KL31_GND
8 AkaCAN_Low 20 KL31_GND
9 BMU-ID_0 21 PublicCAN_GND_Out
10 BMU-ID_1 22 PublicCAN_GND_Out
11 BMU-ID_4 23 AkaCAN_High
12 KL30

Pins 12/13 (KL30), 14/15 (KL15_Wake), 4/5 (KL30_Safe) and 19/20 (KL31_GND) are redundant pairs — in a multi-tray harness they are used for daisy chaining. For a single tray, one of each pair is enough.

AkaCAN is the battery's internal private bus. Leave pins 8 and 23 unconnected.

The BMU-ID pins set the BMU's CAN address through enumerator bridges in the harness. For a single tray you want Tray 01, which needs two bridges: AD2 – AD3 and AD0 – AD1. This gives the BMU address 0xF3, which is what the driver expects.

Parameter Value
LV supply voltage 24 V nominal (see note above — 12 V is mentioned elsewhere in the manual, but no range is published)
Consumption — operation 18.9 W (≈0.8 A at 24 V)
Consumption — standby 8 W (≈0.33 A at 24 V)
Consumption — sleep 4.6 mW
Consumption — peak start Not specified in the manual
CAN type 250 kbit/s, 29-bit extended (SAE J1939). 120 Ω termination must be in the harness — the BMU does not terminate
Contactor Control Not used. The battery closes its own contactors over CAN; the BE contactor pins drive KL30 / KL30_Safe / Wake

Wiring, High voltage connector~

The HV connector is an HVP800. HV+ is on pin 2 and HV− on pin 1. HV wires must be shielded.

PIN CONNECTION
HV 1 High voltage negative pole
HV 2 High voltage positive pole
HVIL 1 HV interlock sink (low voltage signal)
HVIL 2 HV interlock source (low voltage signal)
Parameter Value
Interlock Required Yes
Number of Interlocks 1 (HVIL pair inside the HV connector)

Earthing: the tray has M8 earthing bolts, tightened to 20 Nm, thread depth 11 mm. Bolt material minimum A2-70. Bond the housing before energising anything.

Troubleshooting tips~

Battery never appears on CAN, or the driver sees nothing at all. Check the BMU-ID enumerator bridges first. Without the Tray 01 bridges (AD2 – AD3 and AD0 – AD1) the BMU claims address 0x00 instead of 0xF3, and every message ID shifts with it. There is no 0x00 tray identity anywhere in the CAN matrix, so an unbridged BMU can also raise a generic configuration error.

Battery reports Error and will not leave it, even after a power cycle. The Akasol Error state latches. Warnings and alarms can clear themselves; Error cannot. Per the manual you must deactivate Battery_Wake, fix the underlying cause, and redo the full start-up sequence. Simply rebooting the emulator is not enough — the battery itself has to be taken down.

Battery stays in Init and never reaches Standby. KL30_Safe must be stable and bounce-free before req_batuse=1 is sent. If it is applied at the same time as KL30, or if it is noisy, the battery will sit in Init. The driver's timed state machine handles this, but only if the signals actually reach the BMU — measure at the connector rather than at the GPIO.

Contactors never close. Check the HVIL loop. If the external HV cables are not fitted, the interlock is open and the battery will refuse to close its contactors regardless of what the CAN handshake says.

A persistent SCUConfig error bit with everything else healthy. Worth checking the grounding of the 24 V supply before anything else. On one installation the 0 V rail was left floating and the BMU raised SCUConfig continuously; bonding 0 V to PE cleared it. A multimeter showed only 142 mV between 0 V and PE beforehand, so the disturbance was high-frequency common-mode noise that a DMM cannot see — a clean reading does not rule this out.

Reading the fault bits. The "More Battery Info" page shows BMM01 state, both contactor bits, the alive-counter handshake, and all 64 error/alarm/warning bits by name, taken from Akasol's own PublicCAN.sym. BMM01_Error_info additionally reports an internal Errorvalue / Errornumber / ErrDetectDevice triplet — these are undocumented Akasol-internal codes and generally will not map to anything you can act on directly.

Notes for SolaX inverters~

The pack works with the "SolaX Triple Power LFP over CAN" protocol. SolaX battery types describe LFP packs of 16 cells per module, so pick the type whose voltage window is closest to the Akasol's:

  • Battery type 89 (HS25), 13 modules → 665.6 V nominal, 759.2 V max, 50 Ah per string. That is within about 1.6 % of the Akasol's 655 V and 0.4 % of its 756 V ceiling.
  • Contactor workaround: No Workaround.

Because SolaX assumes 208 LFP cells with a 3650 mV ceiling and the Akasol is 180 NMC cells to 4200 mV, the SolaX driver rescales the reported cell voltages to the assumed cell count. Without that, a real pack at high SOC would look like an overvoltage to the inverter.

CAUTION

Working with high voltage is dangerous. Always follow local laws and regulations regarding high voltage work. If you are unsure about the rules in your country, consult a licensed electrician for more information.